Could I help you?
New Sale! View larger

IEC 62271-102 (2018-05)

New product

IEC 62271-102 (2018-05)

IEC 62271-102:2018 High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches

More details

$139.75

-57%

$325.00

More info

IEC 62271-102:2018 applies to alternating current disconnectors and earthing switches, designed for indoor and outdoor installations for nominal voltages above 1 000 V and for service frequencies up to and including 60 Hz.
This second edition cancels and replaces the first edition published in 2001, Amendment 1:2011 and Amendment 2:2013. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
* new numbering according to IEC 17/1025/RQ to harmonize with ISO/IEC Directives, Part 2, and IEEE Std. C37.100.1;
* clause numbering has been aligned with IEC 62271-1:2017;
* the Scope has been extended to cover all indoor and outdoor installations. Consideration of switching devices having disconnecting and/or earthing switch functionalities, apart from other functions, are also covered by this document;
* ratings have been moved from Annexes B, C and E to Clause 5; the order of the subclauses now corresponds to the order of subclauses in Clause 7;
* new rating values for bus-transfer current and bus-transfer voltage have been assigned;
* new class of mechanical endurance for earthing switches has been added (M1);
* subclause 'Rated values of electrical endurance for earthing switches' is now called 'Classification of earthing switches for short-circuit making capability';
* new subclause with ratings for ice-coating has been added;
* new subclause with classification of bus-charging switching capability has been added;
* new withstand requirements for interlocking devices have been added;
* the way to comply with the requirements of the isolating distance of disconnectors has been modified;
* design and construction requirements for position-indicating devices have been modified, aligning the requirements for position indication and signalling;
* the value of the operating force has been changed;
* the test procedures and validation criteria have been revised and modified where necessary;
* requirements for applied voltage during single-phase test on non-simultaneous closing earthing switches have been changed;
* non-verifiable requirements have been deleted;
* a new subclause has been added for testing mechanical interlocking devices;
* the high- and low-temperature test is mandatory if the temperature limits for the service conditions of the apparatus (defined by the manufacturer) are above +40 °C or below -5 °C, and a more detailed testing procedure is given;
* the testing procedure to verify the proper functioning of the position-indicating device allows a more practicable testing for every technology used;
* a new Annex B has been added with title: 'Current-switching capability required of disconnectors and earthing switches';
* a new Annex C has been added with title: 'Tolerances on test quantities for type tests';
* a new Annex E has been added with title: 'Extension of validity of type tests'.

Author IEC
Editor CEI
Document type Standard
Format File
Edition 2.0
ICS 29.130.10 : High voltage switchgear and controlgear
29.130.99 : Other switchgear and controlgear
Number of pages 222
Replace IEC 62271-102 (2001-12)

Year 2018
Document history IEC 62271-102 (2001-12)
IEC 62271-102 AMD 1 (2011-08)
IEC 62271-102 Edition 1.1 (2012-02)
IEC 62271-102 AMD 2 (2013-02)
IEC 62271-102 Edition 1.2 (2013-02)
IEC 62271-102 AMD 1 Corrigendum 1 (2012-01)
Country Switzerland
Keyword IEC62271;IEC 62271-102:2018